Add Machine - Haas NGC Configuration for FactoryWiz

Add Machine - Haas NGC Configuration for FactoryWiz

Haas NGC Configuration for FactoryWiz

 

On the Haas CNC:

1.     Press Setting and move the tab to wired connection. Here you must set the machine IP and Subnet


2.     Next go to SETTINGS tab and search for setting 143. Set 8000 to use TCP port 8000 for communications and save.

3.     Next, search for setting 261 - DPRNT Store Location and set this to TCP from the dropdown and save.

4.     Search for setting 263 and set this to 8001 and save. This is the TCP port for DPRNT commands. 

 

On FactoryWiz

 

1.     Login to the system with admin credentials

2.     CONFIGUATION > Licensing

3.     Ensure you have enough Flex licenses allocated on the right panel.

4.     CONFIGURATION > Machine

5.     Add

6.     Type in the name of the new machine. If you already have the same machine type, you can copy an existing machine.

7.     Set the machine type to Haas NGC

8.     Set Monitoring TCP Port to 8000

9.     Set DPRNT TCP Port to 8001

10.  Save machine

11.  Restart the RYM Haas NGC service: CONFIGURATION > Services. Stop the Haas service, wait for it to stop and then start it again.

 

For a video on adding a new machine, click here.


    • Related Articles

    • Haas NGC DPRNT

      How to setup Haas NGC DPRNT to work with FactoryWiz In order DPRNT data to FactoryWiz from a Haas NGC there are a things to set in both the CNC settings and FactoryWiz settings. Before you input any settings, you must decide which TCP port number you ...
    • Add Machine - Mazak Monitoring

      PDF with pictures attached below. In FactoryWiz: Login as an Admin Navigate to CONFIGURATION > MACHINE ADD Input the name of the machine Set the machine type to Mazak Set IP address Save. Navigate to CONFIGURATION > LICENSING Increase the Mazak ...
    • Add machine - Brother C00 CNC Monitoring Configuration

      Applicable to the C Series. FactoryWiz Settings Login as an Admin Navigate to CONFIGURATION > MACHINE ADD Input the name of the machine  Set the machine type to Brother Set the IP address, Brother Type and Port Number (set below, normally 10000) ...
    • Add Machine - Kitamura Anywhere remote for FactoryWiz Monitoring

      Configure Kitamura Anywhere remote for FactoryWiz Monitoring Note. This document does not apply to Junior control. In FactoryWiz: Login as an Admin Navigate to CONFIGURATION > MACHINE ADD Input the name of the machine (make an EXACT note of this ...
    • Haas NGC DPRNT Part Name and Part Count

      For information on configuring the Haas and FactoryWiz with DPRNT, please see this KB Article. Part Name The default part name captured from the Haas NGC is the O number (example O01234). To capture something more meaningful, we can use DPRNT. Make ...